Product Categories
What's New
Addressable Detection
Conventional Detection
Residential Use Dectectors
About us
Business and Technology
Quality Assurance
OEM/ODM/EMS Services
Manufacturing Services
International Approvals
Contact Us
Sales Inquiry
FAQs
|
Product Categories > Conventional Detection > PCO-985
Conventional Detection
Early Gas Detection Solutions PCO-985 Series CO gas detectors
Carbon Monoxide (CO) is the most commonly encountered and pervasive poison in our environment. PCO-985 gas detectors help to identify potentially dangerous and life-threatening situations, when there is high concentration of CO gas in the premises. PCO-985 series gas detectors have sleek modern look, they are lightweight and easy-to-use, yet powerful, dependable and accurate.
Approvals
; can be calibrated to meet either EN50291 or UL2034 standards; manufactured according to ISO9001:2008 procedures.
The Range
| PCO-985 | Carbon Monoxide (CO) Gas detector with Relay Output |
Features and Benefits
- Advanced detection of CO gas in the premises
- Japanese nemoto electrochemical carbon monoxide gas sensor
- Durable sensor head; excellent gas access
- Works with any building automation system or other control device
- Built-in local sounder; alarm level reaches 70 dB
- Magnet-activated sensitivity test
- Easy installation and maintenance
- Low-profile solid housing design
- Five-year limited warranty
Available Options
- N/C (normal/close)-N/O (normal/open) selectable relay output
Specification
| Model |
Type of Gas Sensed |
Volt. DC |
Power Consumption |
Operating Temperature |
Sensitivity |
Output Voltage |
Base Model |
| PCO-985 |
Carbon Monoxide (CO) |
12/24 VDC |
4W |
-10°C~50°C |
UL 2034 70 ppm 60-240 min 150 ppm 10-50 min 400 ppm 4-15 min EN 50291 50 ppm 60-90 min 100 ppm 10-40 min 300 ppm with 3 min |
Relay Output |
P/N854001 |
| Alarm Indicator | LED Continuously emitting red light |
| Humidity | 0 to 95% RH, noncondensing |
| Alarm Contact | For 4-wire: N/O or N/C Operation |
| Form A: 1.0A@30VDC/0.5A@125VAC |
| Dimensions | 100mm (dia) x 46mm (ht) with base |
| Weight | 130g/set with base |
Schematic for installing the detector base
 |
Schematic for top cover of the detector
 |
Suggested installation locations for PCO-985 series gas detectors:
Interested in this product? Send us an Inquiry.